● The actuators are used primarily for the load-dependent control of the
gas flow, oil volume and combustion air volume in connection with the
electronic ratio control LMV5.
● Areas of application are oil and gas burners of medium to larger capacity,
as well as thermal process plants.
● Standards & Certifications:
● The actuators SQM45... / SQM48... are of robust design and have a gear train with only small backlash.
● Control and position feedback take place via a bus system (CAN).
● The actuators are driven by stepper motors and can be positioned with a resolution of 0.1°.
● The running times of the associated controlling elements are varied by the basic unit depending on the burner’s control phase
● Operating voltage AC 2 x 12 V
● Power consumption SQM45 9~15VA
SQM48 26~34VA
● Angular adjustment Max. 90°
● Reproducibility ° 0.2°
● Safety class III according to DIN EN 60730 part 1 and part 2-14
● Degree of protection To EN 60529, IP54
● Environment conditions Operation DIN EN 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
TTemperature range -20...+60 °C
Humidity <95 % r.h.
●Weight SQM45... Approx. 1 kg
SQM48... Approx. 1.6 kg
● Life cycle 250,000 start cycles (CLOSE →OPEN→CLOSE) under load with the rated torque in the entire rotation angle range.2,000,000 control cycles under load with 75% of rated torque in rotation angle range of 10°.