● The LME75/LME76 is a microprocessor-based burner control with 

   matching system components for controlling and supervision of forced 

   draft burners of medium to large capacity.

● Standards and certificates

34


Product features
Specification parameters
Data download
  • Product features

    ● The LME75/LME76 is responsible for commissioning and supervising 1-stage or 2-stage forced draft burners or forced draft burners with pneumatic/mechanical 

       ratio control modulation in continuous operation.

    ● Forced draft burner for liquid fuels/Forced draft burner for gaseous fuels

    ● BC interface for connecting an AZL2 or PC

    ● Lockout reset button (info button)

    ● 3-multi color signal lamp (LED) for operating status and fault status messages (lockout reset button (info button) and 3 additional buttons for operation 

       in conjunction with 3 x 7-segment display)

    ● Analog inputs for load controller DC 0...10 V, DC 0/4...20 mA, 0...135 Ω

    ● 3 x 7-segment display for service, fault and status information

    ● Control for a PWM fan motor

  • Specification parameters

    Mains voltage: 230V 50/60Hz

    Lifetime: The LME75/LME76 has a designed lifetime* of 250,000 burner startup cycles which,  under normal operating conditions in heating mode, corresponds 

       to approx. 10 years of  usage

    ● Power consumption: < 10W

    ● Safety class I 

    ● Safety class IP00

    ● Software class  Class C in accordance with  DIN EN 60730-1:2012 /  DIN EN 60730-2-5:2015  2-channel structure

    ● Reaction time in the event of loss of  flame  Depending on parameter 217.01

    Environmental  conditions Operation Climatic conditions: Class 3K3

                                                 Mechanical conditions: Class 3M2

                                                 Temperature range: -40...+60°C

                                                 Humidity: < 95% relative humidity

                                                 Installation altitude:Installation altitude

    ● Weight: Approx. 490g