● Burner management system for forced draft burners with the main
functions
● Burner control
● Fuel-air ration control
● Boiler controller / load controller
● Automatic burner control systems for burners and appliances burning
gaseous or liquid fuels
● Standards & Certificates:
● Burner control, including gas valve proving
● Electronic fuel-air ratio control for a maximum of 6 actuators
● Optional PID temperature / pressure controller (load controller)
● Optional VSD module
● Optional O2 control and an O2 monitor (with PLL52 and QGO2)
● Operating Voltage: AC120(-15%/+10%) 50/60Hz(±6%)
AC230(-15%/+10%)50/60Hz(±6%)
● Life cycle: The LMV5 burner control has a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode,
correspond to approx. 10 years of usage
● Power consumption: <30W
● Safety class I
● Degree of protection of housing IP00
● Environmental conditions Operation DIN EN 60721-3-3
Climatic conditions: Class 3K3
Mechanical conditions: Class 3M3
Temperature range: -20...+60°C
Humidity: <95% r.h.