● Burner control complete with valve proving system
● Electronic fuel-air ratio control system for a maximum of 6 actuators
● Optional: PID control thermostat / pressurestat (internal load controller)
● Optional variable speed drive control
● Optional O2 control and O2 alarm (with QGC)
● Standards & Certificates:
● Burner contro
● Electronic ratio control
● Gas pressure switch valve proving
● Flue gas recirculation (FGR)
● Fault status messages counter
● Error history
● Restart counter
● Program stop function
● Forced intermittent operation (can be deactivated)
● Low-fire shutdown
● Alarm in case of start prevention
● Parameterizable program times and functions
● Mains voltage: AC230(-15%/+10%) 50/60Hz(±6%)
● Lifetime: The LMV6 has a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode, corresponds to approx.
10 years of service
● Internal consumption: <35W
● Protection class I
● Degree of protection IP00
● Software class C
● Weight. 870g
● Climatic conditions Operation Temperature range: -20...+60°C
Humidity: < 95% r.h.
Installation altitude Max. 2,000 m above sea level