● Modulating, directly ignited forceddraft burners
● Integrated PWM fan motor control via 3-position controller or analog
signal for burners with pneumatic ratio control
● Standards and certificates
● Undervoltage detection
● Electrical remote lockout reset facility
● Accurate control sequence thanks to digital signal handling
● Multicolor indication of error status and operating status messages
● Air pressure supervision with functional check of the air pressure switch during startup and operation
● Restart limitation
● Controlled intermittent operation after max. 24 hours of continuous operation
● BC interface
● Mains voltage: 230V 50/60Hz
● Lifetime: The LME7 has a designed lifetime of 250,000 burner startup cycles which
● Internal consumption: < 10W
● Safety class I
● Degree of protection IP00
● Software class Class C in accordance with DIN EN 60730-2-5:2011 2-channel structure
● Response time in the event of loss of flame: Max. 1s
● Environmental conditions Operation EN 60721-3-3:1994
Climatic conditions Class 3K3
Mechanical conditions Class 3M2
Temperature range -40...+60°C
Humidity < 95% relative humidity
Installation altitude Max. 2,000 m above sea level
● Weight: Approx. 490g